Figure 8. Space thermal profile with a conventional System.

 

    Knowing the amount of time to cool the space and the unit(s) FLA, the kW/hr for the conventional system on design day was 48.60.  The supply fan esp. was assumed at 1.5” w.c. to account for the 4-way diffuser. The energy analysis is shown in Table 2. 

 

Conventional System Design Day
Tonnage # of Units Compressor 1 Compressor 2 Condenser Fan Supply Fan Unit FLA AirBoss FLA Unit Total Amps kW kw/hr 
25 4 18.60 18.60 5.00 6.30 48.50 N/A 194.00 89.24 20.82
20 6 20.00 13.20 5.00 4.93 43.13 N/A 258.78 119.04 27.78
 
Total  220 10   452.78 208.28 48.60


Table 2. Conventional system energy usage.

Using the same design parameters, the AirBoss System was modeled with the equipment list shown in Table 3.

 