Figure 8. Space thermal profile with a conventional System.
Knowing the amount of time to cool the space and the unit(s) FLA, the kW/hr for the conventional system on design day was 48.60. The supply fan esp. was assumed at 1.5” w.c. to account for the 4-way diffuser. The energy analysis is shown in Table 2.
| Conventional System | Design Day | ||||||||||
| Tonnage | # of Units | Compressor 1 | Compressor 2 | Condenser Fan | Supply Fan | Unit FLA | AirBoss FLA | Unit Total Amps | kW | kw/hr | |
| 25 | 4 | 18.60 | 18.60 | 5.00 | 6.30 | 48.50 | N/A | 194.00 | 89.24 | 20.82 | |
| 20 | 6 | 20.00 | 13.20 | 5.00 | 4.93 | 43.13 | N/A | 258.78 | 119.04 | 27.78 | |
| Total | 220 | 10 | 452.78 | 208.28 | 48.60 | ||||||
Table 2. Conventional system energy usage.
Using the same design parameters, the AirBoss System was modeled with the equipment list shown in Table 3.